ALARM DESCRIPTION
The chart recorder is equipped with an alarm system which is activated when the sensor conditions exceed user-set limits. The system consists of a built-in audible piezo-electric beeper and a set of normally open dry relay contacts for activating an external alarm. The contacts are rated for 2 amps at 110Vac or 2 amps at 30Vdc. The contact terminals are mounted on the rear of the recorder (refer to Figure 4-1). In addition, the LCD display will flash upon alarm activation.

Figure 4-1. Alarm/Relay Contacts Location

Checking Alarm Limits
WAIT UNTIL THE UNIT HAS STABILIZED AND THE PENS STOP MOVING BEFORE PRESSING ANY KEYS ON THE KEYBOARD.

  • Depending on the Display Selection Switch position, the display will be in ░C or pH for the alarm limit viewing.

  • The word æhiÆ and the high limit value of the alarm may be seen on the display after pressing the ôHIGHö button on the front panel.

  • The word æloÆ and the low limit value of the alarm may be seen on the display after pressing the ôLOWö button on the front panel.


  • NOTE: The alarm limits are stored in permanent EEPROM memory and will not be lost even if power is interrupted and battery backup fails.

    Unlocking/Locking the Control Panel Door
    To access the Alarm Display Buttons (Figure 1-1, item #10) under the control panel door, you may have to unlock the door. YouÆll find the control panel door lock to the left of the control panel. Refer to Figure 4-2.
    Location of the Door Lock
    Figure 4-2. Location of the Door Lock

    Unlocking the Control Panel Door
    Use a small screwdriver to turn the lock to the left as far as it will go. Figure 4-3 shows the unlocked position.
    Door Unlock Position
    Figure 4-3. Door Unlock Position
    Locking the Control Panel Door
    Use a small screwdriver to turn the lock to the right as far as it will go. Figure 4-4 shows the locked position
    .
    Door Lock Position
    Figure 4-4. Door Lock Position

    Setting/Changing Alarm Limits

    Figure 4-5
    Alarm Display Buttons (HIGH/SET/LOW)
    To set the alarm limits on the alarm recorder:

    1. Set the display selection switch (Figure 1-1, item #12) to pH or ░C, depending on the parameter for which you would like to set the alarm limits. Refer to Figure 3-8 for the location of the switch.

    2.
    Open the control panel door (unlock it, if necessary).

    3. Press the ôSETö button to activate the display to set either the high OR low alarm limit. At this time, ôSEö is displayed. Figure 4-5 shows the location of the Alarm Display Buttons.

    4. Release the ôSETö button. The display will alternately flash ôhiö and ôloö repeatedly.

    5a. To change the high alarm limit:
    • Press and hold the ôHIGHö button for 4 seconds, then release. æhiÆ is displayed and then the current high alarm limit is displayed.

    • Press the ôHIGHö or ôLOWö button to respectively increase or decrease the value.

    • Press the ôSETö button to lock in the value(s); the display now shows ôSAö.

    • Continue to step 6.


    5b. To change the low alarm limit:
  • Press and hold the ôLOWö button for 4 seconds, then release. æloÆ is displayed and then the current low alarm limit is displayed.

  • Press the ôHIGHö or ôLOWö button to respectively increase or decrease the value.

  • Press the ôSETö button again to lock in the value(s); the display now shows ôSAö.


  • NOTE: If, after about 15 seconds, you donÆt press the ôSETö button to enter the desired value, the alarm recorder returns the display to the normal operation.

    You can double check your limits at any time by pressing the ôHIGHö and ôLOWö buttons.

    6. Go through steps 1-5 to check and/or change the limits for the other parameters. For example, if you already checked or changed ░C, you may check or change pH if you choose.
    7. After you are all done with the changes, close and lock the control panel door, if necessary.

    Turning the Alarm Off
    If the high or low alarm limit for pH or temperature is exceeded, you will hear the alarm. In addition, if the unit is operating under battery power and the batteries are about to fail, you will hear the alarm.

    The alarm will stay on even after the condition which caused the alarm disappears. Refer to the example below:

    Temp High Limit
    Actual Temp.
    Alarm Sounding
    75░
    74░
    OFF
    75░
    75░
    ON (temp rises)
    75░
    74░
    ON (temp drops) ***

    ***The alarm stays on even though the temperature drops below the limit. The alarm recorder will not reset automatically.

    1. Unlock the control panel door if necessary.
    2. After the alarm becomes activated, the ôSETö button must be pressed to disable it.

    The message ôAOö appears in the display. The alarm is disabled for 10 seconds. After 10 seconds, the alarm may activate again, but only if an alarm condition is present.

    If the alarm is activated and you wish to change the alarm limits:
    a. Press the ôSETö button for 5 seconds. First ôAOö, then ôSEö message will appear in the display.
    b. You can now proceed with the changing the alarm limits as described in Section 4.4.
    c. After you are all done with the changes, lock the control panel door if necessary.

    Disabling the Alarm
    1. Unlock the control panel door if necessary.

    2. On power up, when you hold the ôLOWö button down, an ôAOö message appears in the display and the beeper sounds. This will disable the alarm function.

    (This action sets the high pH limit to 121, the low pH limit to 01, the high temperature limit to 99, and the low temperature limit to 01. Since these limits are outside the normal measuring range of the alarm recorder, the alarm function is effectively disabled.)

    The alarm limits are set this way when you receive the unit. If the alarm is disabled, you must re-initialize the instrument. After you are done with the changes, lock the door if necessary.

    3. To verify the settings after re-initializing is completed, press the ôLOWö button to get the low value, and the ôHIGHö button to get the high value.
    Help Price List Specifications Print Manual Manuals Home
     Home Home  Table of Contents TOC  Back Back  Next Next